What is the maximum number of escape sign/safety luminaires that may be connected to a final circuit?

No more than 20 emergency luminaires with a total load of not more than 60 % of the rated current of the overcurrent
of no more than 60 % of the rated current of the overcurrent protective device.
Source: DIN VDE V 0100-560-1:2022.