07.11.2016 [SW-Version 1.10] SAFELOG SL500

Bootloader:
- If the Busmaster component of the SL-500 is updated, errors may occur with large update files.

Bug fixing:
- The interval for B-tests is now displayed in the menu like the one set before.
- At the start of a service F- and B-test the system checks if the fixture in its version knows this and sends, depending on the version, a service F-Test command or a normal F-test command.
- Service F- and B-tests are only executed if all luminaires can accept this command. If a luminaire contains an old software and the system therefore does not send a service command but a normal command, the luminaire cannot start as long as the battery is sufficiently charged. In this case a message will be shown in the display (""X-Test not possible! Let batteries charge!""), so that some luminaires are not ready yet.

Additional functionality:
- It is possible to give a serial number via a programming adapter during the final inspection of the system.
- Improvement of import and export functions
     a) Output of a readme file to the USB stick with export function
              README Safelog export/import
              The files are in CSV format, please edit only with a text editor or Excel.
              All text inputs must be in UTF-8 charset ! (no special characters, like ;,.)
              Please modify only the colum name in Safelog_Timer.csv and Safelog_Group.csv
              Please modify at Safelog_Node.csv only the colums name (20 characters) and
              detail (80 character).
     b) Simplification of the luminaire table file (Nodes), the luminaire number is now in the table as it is listed in the device. 
         For this purpose a second version of the output file has been created.
     c) Recognition and processing of the old and new version of the luminaire table file, i.e. old
         luminaire table files can still be read correctly by SAFELOG.
- Software version of each luminaire can now be displayed in the consumer details